07.B.05 Means of Egress.

  1. Means of egress must be illuminated, with emergency and non-emergency lighting, to provide a minimum of 5 lm/ft2, (55 lx), measured at the floor. > Reference IESNA Handbook.
  2. The illumination must be arranged so that the failure of any single lighting unit, including the burning out of an electric bulb, will not leave any area darkened to the point of impeding the means of egress.

07.B.06 If work is to be performed at night, a night operations lighting plan must be developed to ensure that all activities, areas and operations are adequately illuminated to perform work safely. On-task lighting must be in conformance with Table 7-1. Lighting near roadways and other public transportation areas must be positioned as to avoid creating a glare hazard.

Facility or Function Lux Foot-candles (lm/ft2)
Accessways
- general indoor
- general outdoor
- exitways, walkways, ladders, stairs

55
33
110

5
3
10
Administrative areas (offices, drafting and meeting rooms, etc.)
540 50
Chemical laboratories 540 50
Construction areas
- general indoor
- general outdoor
- tunnels and general underground work
areas (min 110 lux required at
tunnel/shaft heading during
drilling, mucking, and scaling)

55
33
55

5
3
5
Conveyor routes 110 10
Dam Operating Areas (Interior)
-Tunnels and underground work areas
-Control Stations

55
150

5
15
Docks and loading platforms 33 3
Elevators, freight and passenger 50 5
Temporary Electrical Panels (Interior) 300 30
Temporary Electrical Panels (Exterior) 50 10
First-aid stations and infirmaries 300 30
Maintenance/operating areas/shops
- vehicle maintenance shop
- carpentry shop
- refueling area, outdoors
- shops, fine - medium detail work
- welding shop

300
110
55
540-325
300

30
10
5
50-30
30
Mechanical/electrical equipment rooms 110 10
Outdoor parking areas 33 3
Toilets, wash, and dressing rooms 110 10
Visitor areas 215 20
Warehouses and storage rooms/areas
- indoor rack storage
- outdoor storage

270
33

25
3
Work areas – general (not listed above) 325 30

Knowledge Check Choose the best answer for the question.

7-3. Which of the following is true if any single lighting unit fails in a work area?